Technical Data
Voltage Rating : H05V2-K 0.5 to 1 mm² – 300 / 500V, H07V2-K 1.5 to 35 mm² – 450 / 750V
Temperature Range : -30°C to +90°C
Minimum Bending Radius :
Cable diameter ≤ 8 mm : 4 x outer diameter
Approx. diameter > 8 to 12 mm : 5 x outer diameter
Approx. diameter > 12 mm : 6 x outer diameter
Test Voltage : 2500V
Construction
Conductor Class 5 flexible plain / metal coated stranded according to EN 60228.
Insulation PVC (Polyvinyl Chloride) TI3 to BS EN 50363 – 3.
Properties
PVC self-extinguishing and flame retardant according to EN 60332-1-2.
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.
By adding the suffix (in place of ‘c’) for the conductor type required:
0 = Annealed Bare Copper (ABC), 1 = Annealed Tinned Copper (ATC).
Part Number |
Nominal CrossSectional Area (Sq. mm) |
Nominal Thickness of Insulation (mm) |
Mean Overall Diameter |
Approx. Cable Weight (kg/km) |
Lower Limit (mm) |
Upper Limit (mm) |
H05V2-K |
02030101xx3c |
0.5 |
0.6 |
2.1 |
2.5 |
8.5 |
02030102xx3c |
0.75 |
0.6 |
2.2 |
2.7 |
11.5 |
02030103xx3c |
1 |
0.6 |
2.4 |
2.8 |
13.5 |
H07V2-K |
02030104xx3c |
1.5 |
0.7 |
2.8 |
3.4 |
20 |
02030105xx3c |
2.5 |
0.8 |
3.4 |
4.1 |
32 |
02030106xx3c |
4 |
0.8 |
3.9 |
4.8 |
46 |
02030107xx3c |
6 |
0.8 |
4.4 |
5.3 |
65 |
02030108xx3c |
10 |
1.0 |
5.7 |
6.8 |
110 |
02030109xx3c |
16 |
1.0 |
6.7 |
8.1 |
167 |
02030110xx3c |
25 |
1.2 |
8.4 |
10.2 |
257 |
02030111xx3c |
35 |
1.2 |
9.7 |
11.7 |
358 |