Technical Data
Standard: Based on VDE 0812
Voltage grade (not for power installation): 0.14 mm² = 350 V; >/= 0.25 mm² = 500 V
Insulation Resistance: Min. 20 GΩ x cm
Temperature Range: Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
Minimum Bending Radius: Flexing 15 x cable ø. Fixed installation 6 x cable ø
Test Voltage: Up to 0.25 mm² : 1200 V; > 0.34 mm²: 1500 V.
Mutual capacitance (approx.)
Up to 0.34 mm²
C/C = 120 nF/km. C/S = 160 nF/km.
0.5 mm² to 1.5 mm²
C/C = 160 nF/km. C/S = 240 nF/km.
Inductance: Approx. 0.65 mH/km
Cable Construction
Bare copper, fine wire conductors stranded according to DIN VDE 0295
Special PVC core insulation TI2, to EN 50363-3.
Conductor make-up for
0.14 mm² = 18 x 0.1 mm.
0.25 mm² = 14 x 0.15 mm.
0.34 mm² = 19 x 0.15 mm.
Colour coded to DIN 47100 (Refer table no. 2-2).
Cores stranded in layers with optimal lay-length.
Plastic foil over the laid up cores.
Tinned copper braided screen, approx 85% coverage.
Special PVC outer sheath TM2, to EN 50363-4.1.
Colour grey (RAL 7032).
Properties
PVC self-extinguishing and flame retardant according to EN 60332-1-2.