Technical Data
Standard : UL – Std. 758. Complies to CSA No. 22.2 210 and 127
Nominal Voltage : 600V
Test Voltage (Spark Test)
AWG 22 and 20 = 5kV
AWG 18 to 10 = 6kV
≥ AWG 8 = 7.5kV
Temperature Range : Flexible -5°C to +150°C. Fixed installation -50°C to +150°C
Temperature at Conductor : Max. UL : +150°C
Bending Radius : Approx. 5 x cable ø
Cable Construction
Annealed plain or tinned stranded copper conductor.
XLPE insulation according to UL- Std. 1581 Table 50.232, Complies to CSA No. 22.2 210 and 127.
Properties
PVC self – extinguishing and flame retardant, test method to FT 2
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘z’) for the sheath colour required:
1 – black (RAL 9005), 3 – grey (RAL 7001).
AWG |
Metric Cross Section Area (Sq. mm) |
No. of Strands/Strand Dia. (mm) |
Max. DC Conductor Resistance for ABC @ 20°C (Ω/km) |
Max. DC Conductor Resistance for ATC @ 20°C (Ω/km) |
Insulation Thickness (mm) |
Nominal Cable Diameter (mm) |
21 |
0.5 |
16/0.2 |
43.6 |
46.9 |
0.762 |
2.4 |
19 |
0.75 |
24/0.2 |
27.4 |
29.1 |
0.762 |
2.6 |
18 |
1 |
32/0.2 |
21.8 |
23.2 |
0.762 |
2.8 |
16 |
1.5 |
30/0.25 |
13.7 |
14.6 |
0.762 |
3.1 |
14 |
2.5 |
50/0.25 |
8.62 |
8.96 |
0.762 |
3.5 |
12 |
4 |
56/0.3 |
5.43 |
5.64 |
0.762 |
4.0 |
10 |
6 |
84/0.3 |
3.409 |
3.546 |
0.762 |
4.6 |
8 |
10 |
140/0.3 |
2.144 |
2.23 |
1.143 |
6.1 |
6 |
16 |
126/0.4 |
1.348 |
1.403 |
1.524 |
7.9 |
4 |
25 |
196/0.4 |
0.8481 |
0.882 |
1.524 |
9.1 |
2 |
35 |
276/0.4 |
0.5335 |
0.5548 |
1.524 |
10.7 |
1 |
50 |
296/0.4 |
0.423 |
0.4398 |
2.032 |
12.8 |
Feb-00 |
70 |
360/0.5 |
0.266 |
0.2766 |
2.032 |
14.8 |
Mar-00 |
95 |
480/0.5 |
0.211 |
0.2194 |
2.032 |
16.2 |
Apr-00 |
120.00 |
608/0.5 |
0.1673 |
0.1722 |
2.032 |
17.7 |
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 -violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey, 13 – light blue
Kindly complete the part numbers by adding the suffix (in place of ‘c’) for the conductor type required:
0 = annealed bare copper (ABC), 1 = annealed tinned copper (ATC)
AWG |
Metric Cross Section Area (Sq. mm) |
No. of Strands/Strand Dia. (mm) |
UL 3289 |
UL 3321 |
UL 3173 |
UL 3271 |
UL 3344 |
21 |
0.5 |
06090101xx9c |
06090116xx9c |
06090131xx9c |
06090146xx9c |
06090161xx9c |
19 |
0.75 |
06090102xx9c |
06090117xx9c |
06090132xx9c |
06090147xx9c |
06090162xx9c |
18 |
1 |
06090103xx9c |
06090118xx9c |
06090133xx9c |
06090148xx9c |
06090163xx9c |
16 |
1.5 |
06090104xx9c |
06090119xx9c |
06090134xx9c |
06090149xx9c |
06090164xx9c |
14 |
2.5 |
06090105xx9c |
06090120xx9c |
06090135xx9c |
06090150xx9c |
06090165xx9c |
12 |
4 |
06090106xx9c |
06090121xx9c |
06090136xx9c |
06090151xx9c |
06090166xx9c |
10 |
6 |
06090107xx9c |
06090122xx9c |
06090137xx9c |
06090152xx9c |
06090167xx9c |
8 |
10 |
06090108xx9c |
06090123xx9c |
06090138xx9c |
06090153xx9c |
06090168xx9c |
6 |
16 |
06090109xx9c |
06090124xx9c |
06090139xx9c |
06090154xx9c |
06090169xx9c |
4 |
25 |
06090110xx9c |
06090125xx9c |
06090140xx9c |
06090155xx9c |
06090170xx9c |
2 |
35 |
06090111xx9c |
06090126xx9c |
06090141xx9c |
06090156xx9c |
06090171xx9c |
1 |
50 |
06090112xx9c |
06090127xx9c |
06090142xx9c |
06090157xx9c |
06090172xx9c |
2/0 |
70 |
06090113xx9c |
06090128xx9c |
06090143xx9c |
06090158xx9c |
06090173xx9c |
3/0 |
95 |
06090114xx9c |
06090129xx9c |
06090144xx9c |
06090159xx9c |
06090174xx9c |
4/0 |
120.00 |
06090115xx9c |
06090130xx9c |
06090145xx9c |
06090160xx9c |
06090175xx9c |