Technical Data
Flame Propagation : EN 60332-1-2
Operating Temperature Range : -30°C to +90°C
Bending Radius : 10 x cable diameter
Operating Voltage : 500V
*Also available in 300V variant on request
Marking : RR KABEL RE-2X(St)YSWAY cxa 500V EN 50288-7 CE + 0001m
c – No. of cores
a – Cross sectional area
Cable Construction
Conductor : Annealed copper wires according to BS EN 60228
Insulation : Cross-linked polyethylene XLPE
Colour Code : Black, continuously numbered in white
Wrapping : 1 layer of PETP tape
Collective Screen : Aluminium / PETP tape over tinned copper drain wire
Inner Sheath : Polyvinyl chloride PVC
Armour : Galvanised round steel wires
Cable Sheath : Polyvinyl chloride PVC (Also available in halogen free construction, on request.)
Colour : Black. Blue for intrinsically safe system
Electrical Properties
Conductor Cross Section (Sq.mm) |
Class of Conductor |
No. of Strands/Max. Strand Diameter (mm) |
Max. DC Conductor Resistance at 20°C (Ω/km) |
Max.L/R Ratio (μH/Ω) |
Min. Insulation Resistance (GΩ x cm) |
Max. Mutual Capacitance (nF/km) |
Max. Inductance (mH/km) |
Test Voltage Vrms (Core-Core) |
Test Voltage Vrms (Core-Screen) |
0.5 |
2 |
7/0.3 |
36.0 |
25 |
5000 |
150 |
1 |
2000 |
2000 |
0.5 |
5 |
16/0.2 |
39.0 |
25 |
5000 |
150 |
1 |
2000 |
2000 |
0.75 |
2 |
7/0.37 |
24.5 |
25 |
5000 |
150 |
1 |
2000 |
2000 |
0.75 |
5 |
24/0.2 |
26.0 |
25 |
5000 |
150 |
1 |
2000 |
2000 |
1 |
2 |
7/0.43 |
18.1 |
25 |
5000 |
150 |
1 |
2000 |
2000 |
1 |
5 |
32/0.2 |
19.5 |
25 |
5000 |
150 |
1 |
2000 |
2000 |
1.5 |
2 |
7/0.53 |
12.1 |
40 |
5000 |
150 |
1 |
2000 |
2000 |
2.5 |
2 |
7/0.67 |
7.41 |
60 |
5000 |
150 |
1 |
2000 |
2000 |