Technical Data
Voltage Rating : UO / U – 300 / 500V
Test Voltage : 2000V
Temperature Range : -50°C to +180°C (up to + 220°C for short time)
Temperature Limit at the Conductor : In operation +180°C
Insulation Resistance : Min. 200 MΩ x km
Minimum Bending Radius : Flexing 10 x cable ø. Fixed Installation 5 x cable ø
Cable Construction
Tinned copper conductor to Cl. 5, EN 60228.
Silicone core insulation.
Core identification to DIN VDE 0293 – 308 colour coded or black cores with continuous white numbers.
For 2 – cores brown, blue.
For 3 – cores and above cable provided without protective conductor.
For 6 – cores and above all black cores with number coding.
Cores stranded in layers with optimal lay – length.
Outer jacket of Silicone.
Jacket colour – red brown.
Glass fibre tape over the jacket.
Galvanised steel wire outer braiding.
Galvanised steel braid over the sheath protects against the external mechanical damages;the cable has better durability in harsh environments and applications compared to the conventional silicone cables.ö
Advantages : Hardly changes of dielectric strength and the insulation resistance also at high temperatures, high ignition or flash point, in case of fire, forms an insulating layer of SiO2.
Resistant to : High molecular oils, fats from vegetables and animals, alcohols, plasticisers and clopenes, diluted acids, dyes and salt dissolution, oxidation substances, tropical influences and weather, lake water, oxygen and UV.
Halogen – Free : According to IEC 60754 – 2.
Behavior in Fire : Flame propagation test according to EN 60332 – 1 – 2.