Technical Data
Voltage Rating : 1.5 mmsquare to 35 mmsquare – 300 / 500V
Temperature Range : -15°C to 70 °C
Minimum Bending Radius
Upto 10 mm2 : 10 X Overall Diameter.
16 & 35 mm2 : 12 X Overall Diameter.
16 & 35 mm2 : 12 X Overall Diameter.
Test Voltage : 2 kV for 15 min
Cable Construction
Conductor :
Plain annealed copper conductor : 1.5 & 2.5 mm2 Class -1, 4.0 to 35 mm2 stranded Class 2 complying with BS EN 60228, HD 383, IEC 60228.
Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3
Sheath : PVC (Polyvinyl Chloride ) compound type Type 6 complying with BS 7655-4.2
Insulation Colours : Blue and brown
Sheath Colour : Grey RAL 7001
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 – blue, 09 – brown
Part Number |
Nominal Cross Sectional Area (Sq. mm) |
Nominal Insulation Thickness (mm) |
Nominal Sheath Thickness (mm) |
Overall Diameter Lower Limit (mm) |
Overall Diameter Upper Limit (mm) |
Approx. Net Weight (kg/km) |
01150101xx10 |
1.5 |
0.70 |
0.8 |
4.20 |
5.00 |
37 |
01150102xx10 |
2.5 |
0.80 |
0.8 |
4.80 |
5.70 |
51 |
01150103xx10 |
4 |
0.80 |
0.9 |
5.50 |
6.70 |
75 |
01150104xx10 |
6 |
0.80 |
0.9 |
6.00 |
7.30 |
98 |
01150105xx10 |
10 |
1.00 |
0.9 |
7.30 |
8.80 |
152 |
01150106xx10 |
16 |
1.00 |
1.0 |
8.40 |
10.10 |
220 |
01150107xx10 |
25 |
1.20 |
1.1 |
10.00 |
12.10 |
336 |
01150108xx10 |
35 |
1.20 |
1.1 |
11.10 |
13.50 |
353 |
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 – blue, 09 – brown.