Technical Data
Standard: Adapted to DIN 19245 & EN 50170
Operating Voltage: 250V (not for power installation)
Insulation Resistance: 5000 G x cm
Temperature Range: Flexing 12 x cable ø Fixed 6 x cable ø
Minimum Bending Radius: Flexing 12 x cable ø.
Fixed installation 6 x cable ø
Test Voltage: 1500V
Flame Retardant: Complies to IEC 60332-1-2
Electrical Parameters
Conductor Resistance (Loop) at 20°C : 110 /km (Max.)
Mutual Capacitance : 35 nf/km (Max.)
Inductance : 0.65 mH/km (Nom.)
Frequency |
Characteristic Impedance (Ω) |
Attenuation (dB/100m) |
9.6 kHz |
270 ± 27 |
≤ 0.25 |
38.4 kHz |
185 ± 18.5 |
≤ 0.40 |
4 MHz |
150 ± 15 |
≤ 2.2 |
16 MHz |
150 ± 15 |
≤ 4.2 |
PROcess FIeld BUS PA:
Conductor Resistance (Loop) at 20°C : 44 /km (Max.)
Mutual Capacitance : 55 nf/km (Max.)
Characteristic Impedance @ 31.25 kHz : 100 ± 15
Attenuation @ 39 Khz : ≤ 3 dB/km
Inductance : 0.65 mH/km (Nom.)
Baud Rate (kbit/s) |
Segment Length (Meters) |
Segment Length (Feet) |
9.6 |
1200 |
3940 |
19.2 |
1200 |
3940 |
45.45 |
1200 |
3940 |
93.75 |
1200 |
3940 |
187.5 |
1000 |
3280 |
500 |
400 |
1310 |
1500 |
200 |
656 |
3000 |
100 |
328 |
6000 |
100 |
328 |
12000 |
100 |
328 |
More Variants Available
PROcess FIeld BUS DP and PA for flexible applications
PROcess FIeld BUS DP and PA with steel braid
Halogen free variant with Low Smoke Zero Halogen (LSZH) outer sheath.
Note :
HART = Highway Addressable Remote Transducer DP = Decentralized Peripherals
PA = Process Automation