RE-Y(St)YSWAY – SINGLE & MULTI-PAIR

RE-Y(St)YSWAY – SINGLE & MULTI-PAIR

Standard

Adapted to EN 50288-7

Technical Data

Flame Propagation: EN 60332-1-2
Operating Temperature Range: -30°C to +70°C
Bending Radius: 10 x cable diameter
Operating Voltage: 500V
*Also available in 300V variant on request.
Marking: RR KABEL RE-Y(St)YSWAY nxmxa 500V EN50288-7 CE + 0001m
n – No. of pairs
m – Pairs
a – Cross sectional area

Cable Construction

Conductor: Annealed copper wires according to BS EN 60228
Insulation: Polyvinyl chloride PVC
Pairs: Twisted
Identification Pairs: Black & white, continuously numbered on white core (1, 2, 3…) for multi-element
Wrapping: 1 layer of PETP tape
Collective Screen: Aluminium / PETP tape over tinned copper drain wire
Inner Sheath: Polyvinyl chloride PVC
Armour: Galvanised round steel wires
Cable Sheath: Polyvinyl chloride PVC
Colour: Black. Blue for intrinsically safe system

Electrical Properties

Conductor Cross Section (Sq.mm) Class of Conductor No. of Strands/Max. Strand Diameter (mm) Max. DC Conductor Resistance* at 20°C (Ω/km) Max.L/R Ratio (μH/Ω) Min. Insulation Resistance (GΩ x cm) Max. Mutual Capacitance (nF/km) Max.Inductance (mH/km) Test Voltage Vrms (Core-Core) Test Voltage Vrms (Core-Screen)
0.5 2 7/0.3 36.0 25 20 250 1 2000 2000
0.5 5 16/0.2 39.0 25 20 250 1 2000 2000
0.75 2 7/0.37 24.5 25 20 250 1 2000 2000
0.75 5 24/0.2 26.0 25 20 250 1 2000 2000
1 2 7/0.43 18.1 25 20 250 1 2000 2000
1 5 32/0.2 19.5 25 20 250 1 2000 2000
1.5 2 7/0.53 12.1 40 20 250 1 2000 2000
2.5 2 7/0.67 7.41 60 20 250 1 2000 2000

*For multi-pair maximum resistance shall be increased by 2%.

Quick Inquiry